  • 耐火电力电缆.png

Fire-resistant Power Cable

This product is suitable for fixed installation in 0.6/1kV rated voltage power transmission and distribution lines. During operation, in addition to reliably transmitting electricity under normal conditions, the cable can maintain uninterrupted current flow for a certain period even when exposed to fire or combustion.

Share to

  • Product Description
  • Application

    This product is designed for fixed installation in 0.6/1kV rated power transmission and distribution lines. During operation, in addition to reliably transmitting electricity under normal conditions, the cable maintains uninterrupted current flow for a limited time even when exposed to fire or combustion. The cable conductor is permitted to operate at a maximum temperature of 70°C, while its temperature during a short-circuit event will not exceed 160°C for no more than 5 seconds.

    Model and Name

    Model

    Name

    NH-YJV

    Cross-linked polyethylene-insulated, PVC-sheathed fire-resistant power cable

    NH-VV₂₂

    Copper-core PVC-insulated steel-tape armored PVC-sheathed fire-resistant power cable

    NH-YJV₂₂

    Cross-linked polyethylene-insulated, steel-tape-armored, PVC-sheathed fire-resistant power cable

    Cable Laying Recommendations

    1. The cable and ambient temperature must be above 0°C or maintained at this condition for 24 hours.

    2. The minimum bending radius should be no less than: for single-core cables — 30(D + d), and for multi-core cables — 22.5(D + d), where D is the actual outer diameter of the cable, and d is the actual diameter of the conductor.

    Fire-Resistant Cable Technical Data Sheet

    Product Specifications
    Number of cores × Nominal cross-section
    Conductor Structure
    Number of filaments / Monofilament diameter
    Fire-resistant insulation
    Nominal thickness
    Plastic insulation
    Nominal thickness
    Outer Protective Layer
    Nominal thickness
    Cable
    Approximate Outer Diameter
    Maximum conductor
    DC resistance
    Cable
    Approximate weight
    Cable
    Current-carrying capacity
    Air cabling
    N×mm² N/mm mm mm mm mm Ω/km Kg/km A
    1 × 10 7 / 1.38 0.5 1 1.8 11 1.83 186 77.2
    1 × 16 7 / 1.76 0.5 1 1.8 12 1.15 254 102.7
    1 × 25 7 / 2.24 0.5 1.2 1.8 13.8 0.727 361 136.7
    1 × 35 7 / 2.55 0.5 1.2 1.8 14.8 0.524 468 164.3
    1 × 50 4/1.76 + 8/2.55 0.5 1.4 1.8 16.4 0.387 639 199.3
    1 × 70 14 / 2.55 0.5 1.4 1.8 18.2 0.268 846 250.1
    1 × 95 19 / 2.55 0.5 1.6 1.8 20.2 0.193 1120 302
    1 × 120 4/1.76 + 22/2.55 0.5 1.8 1.8 21.6 0.153 1365 353.9
    1 × 150 30 / 2.55 0.5 1.8 1.8 23.6 0.124 1691 407.2
    1 × 185 37 / 2.55 0.5 2 1.8 25.6 0.0991 2063 462.7
    1 × 240 48 divided by 2.55 0.5 2.2 1.9 28.4 0.0754 2634 554.4

    Product Specifications
    Number of cores × Nominal cross-section

    Conductor Structure
    Number of filaments / Monofilament diameter

    Fire-resistant insulation
    Nominal thickness

    Plastic insulation
    Nominal thickness

    Outer Protective Layer
    Nominal thickness

    Cable
    Approximate Outer Diameter

    Maximum conductor
    DC resistance

    Cable
    Approximate weight

    Cable
    Current-carrying capacity
    Air cabling

    N×mm²

    N/mm

    mm

    mm

    mm

    mm

    Ω/km

    Kg/km

    A

    2 × 10

    7 / 1.38

    0.5

    1

    1.8

    19.6

    1.83

    487

    59.6

    2 × 16

    7 / 1.76

    0.5

    1

    1.8

    21.6

    1.15

    645

    77.4

    2 × 25

    7 / 2.24

    0.5

    1.2

    1.8

    25.2

    0.727

    907

    99.4

    2 × 35

    7 / 2.55

    0.5

    1.2

    1.8

    27.2

    0.524

    1157

    119.1

    2 × 50

    4/1.76 + 8/2.55

    0.5

    1.4

    1.9

    30.6

    0.387

    1552

    140.4

    2 × 70

    14 / 2.55

    0.5

    1.4

    2.1

    34.6

    0.268

    2066

    168.7

    2 × 95

    19 / 2.55

    0.5

    1.6

    2.2

    38.8

    0.193

    2701

    203.5

    2 × 120

    4/1.76 + 22/2.55

    0.5

    1.8

    2.3

    41.8

    0.153

    3280

    227

    2 × 150

    30 / 2.55

    0.5

    1.8

    2.4

    46

    0.124

    4029

    255.9

    Product Specifications
    Number of cores × Nominal cross-section

    Conductor Structure
    Number of filaments / Monofilament diameter

    Fire-resistant insulation
    Nominal thickness

    Plastic insulation
    Nominal thickness

    Outer protective layer
    Nominal thickness

    Cable
    Approximate Outer Diameter

    Maximum conductor
    DC resistance

    Cable
    Approximate weight

    Cable
    Current-carrying capacity
    Air cabling

    N×mm²

    N/mm

    mm

    mm

    mm

    mm

    Ω/km

    Kg/km

    A

    3 × 10

    7 / 1.38

    0.5

    1

    1.8

    20.8

    1.83

    617

    52.3

    3 × 16

    7 / 1.76

    0.5

    1

    1.8

    22.9

    1.15

    831

    69.1

    3 × 25

    7 / 2.24

    0.5

    1.2

    1.8

    26.8

    0.727

    1195

    89.3

    3 × 35

    7 / 2.55

    0.5

    1.2

    1.9

    29.2

    0.524

    1557

    107.4

    3 × 50

    4/1.76 + 8/2.55

    0.5

    1.4

    2

    32.8

    0.387

    2105

    128.8

    3 × 70

    14 / 2.55

    0.5

    1.4

    2.1

    36.9

    0.268

    2813

    158.1

    3 × 95

    19 / 2.55

    0.5

    1.6

    2.3

    41.7

    0.193

    3696

    191.7

    3 × 120

    4/1.76 + 22/2.55

    0.5

    1.8

    2.4

    44.9

    0.153

    4506

    200.5

    3 × 150

    30 / 2.55

    0.5

    1.8

    2.6

    49.6

    0.124

    5580

    249.3

    3 × 185

    37 / 2.55

    0.5

    2

    2.7

    51.4

    0.0991

    6787

    283.7

    3 × 240

    48 divided by 2.55

    0.5

    2.2

    2.9

    60.1

    0.0754

    8655

    331.6

    Product Specifications
    Number of cores × Nominal cross-section

    Conductor Structure
    Number of filaments / Monofilament diameter

    Fire-resistant insulation
    Nominal thickness

    Plastic insulation
    Nominal thickness

    Outer Protective Layer
    Nominal thickness

    Cable
    Approximate Outer Diameter

    Maximum conductor
    DC resistance

    Cable
    Approximate weight

    Cable
    Current-carrying capacity
    Air cabling

    N×mm²

    N/mm

    mm

    mm

    mm

    mm

    Ω/km

    Kg/km

    A

    4 × 10

    7 / 1.38

    0.5

    1

    1.8

    22.7

    1.83

    773

    53.9

    4 × 16

    7 / 1.76

    0.5

    1

    1.8

    25.1

    1.15

    1059

    69

    4 × 25

    7 / 2.24

    0.5

    1.2

    1.9

    29.4

    0.727

    1528

    90.4

    4 × 35

    7 / 2.55

    0.5

    1.2

    2

    32.2

    0.524

    1997

    110.6

    4 × 50

    4/1.76 + 8/2.55

    0.5

    1.4

    2.1

    36.3

    0.387

    2721

    131

    4 × 70

    14 / 2.55

    0.5

    1.4

    2.3

    41

    0.268

    3630

    161.4

    4 × 95

    19 / 2.55

    0.5

    1.6

    2.4

    46.1

    0.193

    4808

    196.1

    4 × 120

    4/1.76 + 22/2.55

    0.5

    1.8

    2.6

    49.9

    0.153

    5864

    225.8

    4 × 150

    30 / 2.55

    0.5

    1.8

    2.7

    54.9

    0.124

    7223

    255.1

    4 × 185

    37 / 2.55

    0.5

    2

    2.9

    60.1

    0.0991

    8825

    290.5

    4 × 240

    48 divided by 2.55

    0.5

    2.2

    3.1

    66.8

    0.0754

    11255

    338.8

    Product Specifications
    Number of cores × Nominal cross-section

    Conductor Structure
    Number of filaments / Monofilament diameter

    Fire-resistant insulation
    Nominal thickness

    Plastic insulation
    Nominal thickness

    Outer protective layer
    Nominal thickness

    Cable
    Approximate Outer Diameter

    Maximum conductor
    DC resistance

    Cable
    Approximate weight

    Cable
    Current-carrying capacity
    Air cabling

    N×mm²

    N/mm

    mm

    mm

    mm

    mm

    Ω/km

    Kg/km

    A

    3 × 16 + 1 × 10

    7/1.70
    7 / 1.35

    0.5

    1.0   
    1.0

    1.8

    24.5

    1.15   
    1.83

    993

    69.5

    3 × 25 + 1 × 16

    7/2.24
    7 / 1.70

    0.5

    1.2   
    1.0

    1.9

    28.2

    0.727   
    1.15

    1418

    89.6

    3 × 35 + 1 × 16

    7 / 2.55
    7 / 1.70

    0.5

    1.2   
    1.0

    1.9

    30.5

    0.524   
    1.15

    1770

    109

    3 × 50 + 1 × 25

    4/1.76 + 7/2.55
    7 / 2.55

    0.5

    1.4   
    1.2

    2.1

    34.7

    0.387   
    0.727

    2430

    129.5

    3 × 70 + 1 × 35

    14 / 2.55
    7 / 2.55

    0.5

    1.4   
    1.2

    2.2

    38.9

    0.268   
    0.524

    3230

    160.8

    3 × 95 + 1 × 50

    19 / 2.55
    4/1.76 + 8/2.55

    0.5

    1.6   
    1.4

    2.4

    43.9

    0.193   
    0.387

    4301

    193.9

    3 × 120 + 1 × 50

    4/1.76 + 22/2.55
    4/1.76 + 8/2.55

    0.5

    1.6   
    1.4

    2.5

    47.8

    0.153   
    0.387

    5321

    224

    3 × 150 + 1 × 70

    30 / 2.55
    14 / 2.55

    0.5

    1.8   
    1.4

    2.6

    51.8

    0.124   
    0.268

    6355

    251.9

    3 × 185 + 1 × 120

    37 / 2.55
    19 / 2.55

    0.5

    2.0   
    1.6

    2.8

    57.2

    0.0991   
    0.193

    7685

    287.1

    3 × 240 + 1 × 120

    48 / 2.55
    4/1.76 + 22/2.55

    0.5

    2.2   
    1.6

    3

    63

    0.0754   
    0.153

    9960

    334.4

    Product Specifications
    Number of cores × Nominal cross-section
    Conductor Structure
    Number of filaments / Monofilament diameter
    Fire-resistant insulation
    Nominal thickness
    Plastic insulation
    Nominal thickness
    Outer protective layer
    Nominal thickness
    Cable
    Approximate Outer Diameter
    Maximum conductor
    DC resistance
    Cable
    Approximate weight
    Cable
    Current-carrying capacity
    Air cabling
    N×mm² N/mm mm mm mm mm Ω/km Kg/km A
    3 × 16 + 2 × 10 7/1.70
    7 / 1.35
    0.5 1.0  
    1.0
    1.8 26.5 1.15  
    1.83
    1163 71.4
    3 × 25 + 2 × 16 7/2.24
    7 / 1.70
    0.5 1.2  
    1.0
    1.9 30.9 0.727  
    1.15
    1662 91.2
    3 × 35 + 2 × 16 7 / 2.55
    7 / 1.70
    0.5 1.2  
    1.0
    1.9 32.7 0.524  
    1.15
    2016 110.4
    3 × 50 + 2 × 25 4/1.76 + 7/2.55
    7 / 2.55
    0.5 1.4  
    1.2
    2.2 37.7 0.387  
    0.727
    2802 131.7
    3 × 70 + 2 × 35 14 / 2.55
    7 / 2.55
    0.5 1.4  
    1.2
    2.4 42.1 0.268  
    0.524
    3714 162.2
    3 × 95 + 2 × 50 19 / 2.55
    4/1.76 + 8/2.55
    0.5 1.6  
    1.4
    2.5 47.4 0.193  
    0.387
    4944 197.7
    3 × 120 + 2 × 70 4/1.76 + 22/2.55
    4/1.76 + 8/2.55
    0.5 1.6  
    1.4
    2.6 51.8 0.153  
    0.387
    6216 223
    3 × 150 + 2 × 70 30 / 2.55
    14 / 2.55
    0.5 1.8  
    1.4
    2.7 55.3 0.124  
    0.268
    7263 262
    3 × 185 + 2 × 95 37 / 2.55
    19 / 2.55
    0.5 2.0  
    1.6
    2.9 61.2 0.0991  
    0.193
    9015 290.6
    Product Specifications
    Number of cores × Nominal cross-section
    Conductor structure
    Number of filaments / Monofilament diameter
    Fire-resistant insulation
    Nominal thickness
    Plastic insulation
    Nominal thickness
    Outer protective layer
    Nominal thickness
    Cable
    Approximate Outer Diameter
    Maximum conductor
    DC resistance
    Cable
    Approximate weight
    Cable
    Current-carrying capacity
    Air cabling
    N×mm² N/mm mm mm mm mm Ω/km Kg/km A
    5 × 10 7 / 1.35 0.5 1 1.8 24.8 1.83 945 54.5
    5 × 16 7 / 1.70 0.5 1 1.8 27.5 1.15 1301 71.9
    5 × 25 7 / 2.24 0.5 1.2 2 32.7 0.727 1900 93.1
    5 × 35 7 / 2.55 0.5 1.2 2.1 35.6 0.524 2484 112.5
    5 × 50 4/1.76 + 8/2.55 0.5 1.4 2.3 40.4 0.387 3395 133.7
    5 × 70 14 / 2.55 0.5 1.4 2.4 45.4 0.268 4514 165.3
    5 × 95 19 / 2.55 0.5 1.6 2.6 51.2 0.193 5976 200.8
    5 × 120 4/1.76 + 22/2.55 0.5 1.8 2.7 55.2 0.153 7294 231.1
    5 × 150 30 / 2.55 0.5 1.8 2.9 61 0.124 9037 269.9
    5 × 185 37 / 2.55 0.5 2 3.1 66.8 0.0991 11029 307.4

    Current-carrying capacity correction factors for PVC-insulated power cables under different ambient temperatures:

    Operating temperature
    70°C
    Air °C
    5 10 15 20 25 30 35 40 45 50
    1.47 1.41 1.35 1.39 1.22 1.15 1.08 1 0.91 0.81

Contact Us

Send Email

Phone / Wechat

Phone / Wechat

Keywords:

Request A Quote

*Note: Please fill in the information accurately and keep the communication open. We will contact you as soon as possible.

Submit

Related Products

Equipment wiring refers to conductive materials used to carry electric current between power sources, devices, and systems.
View Details View Details
The continuous operating temperature of mineral cables is 250°C.
View Details View Details
Rubber cables are power cables that use rubber or plastic as the insulating material.
View Details View Details
Primarily used in the energy and power sectors.
View Details View Details
< 12 >